RZ100 smoke control centre
The smoke detector unit RZ100 supplies and controls all the ASSA ABLOY electromechanical hold-open devices
Product description
- The smoke detector unit RZ100 supplies and controls all the ASSA ABLOY electromechanical hold-open devices with 24 VDC. In case of a fire, smoke or power failure the connected hold-open device -integrated into a guide rail or external magnets- will be de
- General type approval as arrester system Z-6.5002364
- Connection of radio-controlled components possible
Overview of Advantages
- The smoke detector unit RZ100 includes a smoke chamber, control-unit and power supply in one cabinet.The unit works by an optical smoke detection with integrated measuring chamber monitoring and optical soiling indicator.
- Indicators: Green LED - operation mode; Red LED - Alarm; Yellow LED (flush) - pollution
- Equipped for the connections of further: smoke detectors; external release button
- Integrated potential-free alarm relay
- Approved for use with all ASSA ABLOY arrester systems
view construction details
Input voltage | 230 V AC |
Output voltage | 24 V DC |
Max. output current | 300 mA |
Class of protection | IP 20 |
General type approval | Z-6.500-2364 |
Ceiling smoke detector | max. 2 pieces (Hekatron ORS142 or TDS247) |
Floating switchover contact | 24 V, switching capacity 1A (ohmic load) |
LED display | Operating/alarm/impurification |
Functional test button | Integrated |
Cable inlet | Surface and flush mount |
Ambient temperature | -5 °C to +50 °C |
Connection terminal | yes |
Order number | Description |
---|---|
DCRZ100---DEV1- | Silver EV1 |
DCRZ100---D9016 | White, similar to RAL9016 |
DCRZ100---D35-- | Stainless steel design |
DCRZ100---DXXXX | Customised finish |
| Order number | Product |
---|---|---|
DCRZ101----9010 | Smoke detector RZ101 ORS 142 with socket; white similar to RAL 9010 | |
DCRZ101AT--9010 | Smoke detector RZ101AT ORS 142 AT; white similar to RAL 9010 | |
DCA175--------- | Test book A175 Arrester systems |