ePED® Escape door terminal
Product description
For use with time delay, with 4-wire BUS cabling in Hi-O technology.
With emergency open module for the control and monitoring of electrical locking elements for escape routes.
The time delay is tested according to the requirements of DIN EN 13637:2015 (electrically controlled exit systems for use on escape routes) as per EN 61508 Safety Integrity Level 2 (SIL2).
Time delay applications are subject to local Building Regulations. Additional permissions may be required.
For mounting in DIN switch boxes for light switch systems with manufacturer-specific covers and frames.
Consists of: Display release delay; emergency open module; key switch module
| Current consumption 24 V DC | 225 mA |
| Inputs | 2 |
| Required power supply | 24 V (±15 %) DC SELV |
| Outputs | 1 x 30 V / 1 A switchover contact |
| Control function | Yes, Hi-O technology |
| Operating and display function | Yes, integrated |
| Connection | 4-wire bus |
| Display of down counter | Yes |
| Control element | Key switch with CH-RC, adjustable lock ward 8 x 45°; 32.5 mm long |
| Initial configuration | With ePED® service interface and software for MS Windows |
| Operating temperature range | -10 °C – +55 °C |
| Area of application | For indoor use |
| Class of protection | IP30 (wenn vollständig montiert) |
| Installation | in switch boxes |
| Dimension | 3-gang switch combination |
| Sabotage switch | Yes |
| Amount of bus addresses | 3 |
| Key switch on opposite side to direction of escape | Yes (without display) |
| Certified in compliance with | EltVTR; DIN EN 13637:2015 |