Escape door control module networkable
System 55 with emergency switch
Product description
To control electric locking elements in doors along escape routes; certified in compliance with EltVTR and DIN EN 13637:2015.
Escape door control module
- Emergency button lights up; features reusable, non-detachable, shatterproof protective cover
- Integrated visual door status indicator with high-performance LEDs (green / red / yellow) signalling unlocked / locked / alarm status
- Acoustic alarm device for alarm systems
- Emergency button actuation sign
- Tamper contact
- Adjustable time periods for max. permanent release, delay permanent release, temporary release, pre-alarm, alarm time, guidance signal
- Monitoring of time door is open in the case of temporary unlocking
- With an input featuring adjustable parameters for:
- Control of locking and unlocking, temporary release, alarm acknowledgement via a potential-free contact in operating devices, such as card readers and door code device, or
- Temporary release using an access control system, or
- Priority locking via burglar alarm system, or
- Unlocking via timer, etc.
- With an input for:
- Emergency release via fire alarm system
- With a relay output featuring adjustable parameters for:
- Door locked/unlocked, or
- Door open/closed, or
- Collective alarm, or
- Individual alarm, or
- Actuation electric strike/motorised lock/swing door operator/arrester system
- Connections:
- SYSCON-4: power supply
- SYSCON-5: operating unit
- Plug-in screw terminals
- Product version: 2
- Model range 1385: TS bus interface for parameterisation using software (FT Manager) and networks for parallel operation of visual display software, panel and OPC server
Scope of delivery
- 1 escape door control module
- 1 operating manual
Note
- Standard for 55 mm modules
Rated voltage | 12-24 VDC SELV |
Output current | Max. 1 A (depending on the power supply used) |
Power consumption | 0.1 A at 24V |
Total power consumption | 0.1A at 24V |
Control | Yes, integrated |
Certified in compliance with | EltVTR; DIN EN 13637:2015 |
TS-Bus interface | Only model series 1385 |
Connection to panel, visualisation system, OPC server | Only model series 1385 |
Stand-alone operation with I/O module | Only model series 1385 |
Stand-alone operation (offline) | Yes |
Emergency switch | Yes |
Control element | No, external operating unit required |
Setting of times and functions | Via key switch, via FT Manager (together with bus controller) |
Operating temperature range | -5 °C to +40 °C |
Class of protection | IP 30 |
Area of application | For indoor use, without condensation |
Dimension | Frame or surface-mounted module required to install flush-mounted switch box 62.5 mm deep |
Inputs | 1 x parametrisable; 1 x fire alarm system |
Outputs | 1x; 30 V / 1 A switchover contact; adjustable parameters |
Key switch on opposite side to direction of escape | Yes (without display) |
Connection | Yes |
Stand-alone operation with I/O module | Yes |