Escape door control unit
24 V DC; offline; without power unit; surface mount
Product description
The control terminal combines both the control device and the door terminal in one housing. One component is inapplicable without limitation at that size of building. Without integrated power supply.
Escape door control module
- Emergency button lights up; features reusable, shatterproof protective cover
- Integrated door status indicator (green / red / yellow) signalling unlocked / locked / alarm status
- Sign emergency button
- alarm signal and tampering contact;
- Key switch to control door
- With Euro profile half cylinder, including 3 keys
- Adjustable time intervals for temporary release, pre-alarm, alarm interval
- Monitoring of time door is open during temporary release.
- Connections: screw terminals
- Model 1340-20
Scope of delivery
- 1 escape door control terminal
Rated voltage | 24 VDC SELV |
Output voltage | 24 V DC |
Power consumption | 0,15 A |
Input voltage | 24 V DC |
Total power consumption | 0.15 A at 24 V |
Output current | for external consumers: max. 0.64 A (depending on the external power supply unit) |
Control | Yes, integrated |
Power supply | External power supply required |
Connection to panel, visualisation system, OPC server | Yes, model 1340–20 |
Configured centrally using FT Manager | No |
Stand-alone operation with I/O module | No |
Stand-alone operation (offline) | Yes |
Emergency switch | Yes |
Control element | Key switch with Euro profile cylinder; cam position 8 x 45°; 30.5 mm long |
Setting of times and functions | Via DIP switches |
Operating temperature range | 0 °C to +40 °C |
Class of protection | IP 20 |
Dimension | (HxWxD) 249x92x98 mm |
Inputs | E1: temporary release; E2: fire alarm system; E3: timer |
Outputs | A1: locked/unlocked; A2: collective alarm, contacts max. 24 V / 1 A |
Key switch on opposite side to direction of escape | Yes |
Certified in compliance with | EltVTR |